Digital Electric Motor Protector ARD3M

● Auxiliary power supply type is optional, AC220V or AC380V

● Rated Voltage: AC220V / 380V / 660V, 50Hz / 60Hz

● Optional leakage protection, RS485 communication, analog output, etc.

● 2-63rd harmonic; 2 MODBUS-RTU communication

● 10 programmable DI inputs

● 6 programmable DO outputs

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
product detail

General

ARD3M intelligent motor protector (hereinafter referred to as the protector) is suitable for low-voltage motor circuits with rated voltage up to 660V and integrates protection, measurement, control, communication, operation and maintenance. Its perfect protection function ensures the safe operation of the motor, with logic programmable function, can meet a variety of control methods. Different communication modules can be selected to meet the needs of field communication.


Function

Protection Type (Default  Active Period)

Whole Course:

Overvoltage, undervoltage, voltage imbalance, phase sequence, external fault, overflow protection, starting times, fault times, running time, PTC/NTC temperature protection, insulation monitoring

When Starting:

Reverse time overload, blocking, phase break, leakage, grounding, starting timeout, short circuit, overflow protection, Overvoltage, undervoltage, voltage imbalance, phase sequence, external fault, number of starts, number of faults, running time, PTC/NTC temperature protection, fixed time overload, insulation monitoring

In Operation:

Reverse time-limit overload, blocking, phase break, current imbalance, leakage, grounding, constant time-limit overload, under load, short circuit, overflow protection, overvoltage, undervoltage, voltage unbalance, phase sequence, underpower, overpower, external fault, PTC/NTC temperature protection, number of starts, number of faults, running time, insulation monitoring

Dimension


Front Panel


 

Wiring

Installation Dimension


FIG. 1 Composition of products with 100A and below specifications

 

FIG. 2 Composition of 250A and 800A

 


FIG. 3 Assembly diagram of main body and optional communication module

 

When install the meter, loosen the locking screw of the fixing bracket, remove the fixing bracket, insert the instrument into the mounting hole, install the fixing bracket and tighten the screw to make the instrument be firmly installed without loosening. Shape for clamp reed squeeze installation.

 

Matched Transformer

The current transformer with the current specification of the protector is 100A, with the standard secondary connection line length of 1m±10cm. If other lengths are needed, please contact the manufacturer, for example, 3m and 5m lines are optional.The secondary lines of yellow, blue, red and black correspond to to the correlation of current A, B, C and the common end of the transformer. A protector is equipped with A set of transformer.

The current specification of the protector is the current transformer matched at 250A. There is no secondary connection wire. One protector is equipped with three transformers.

The protectors with current specifications of 100A and below are equipped with leakage current transformers with specifications of L-45.250A and current protector with specifications L-80 leakage current transformer; 800A and current specification protector with L-150 leakage current transformer. The leakage transformer is equipped with a secondary wire of 2m±10cm. If other lengths are needed, please contact the manufacturer.

 

Typical Connection

PARAMETER
When install the meter, loosen the locking screw of the fixing bracket, remove the fixing bracket, insert the instrument into the mounting hole, install the fixing bracket and tighten the screw to make the instrument be firmly installed without loosening.Shape for clamp reed squeeze installation.
Parameter Technical specification
Auxiliary power supply AC220V(AC85-265V/DC100-300V);Option:AC380V(AC/DC100-415V)
Rated voltage AC220V/380V/660V,50Hz/60Hz
Rated current 1A(0.1-5000A) Specific current transformer
5A(0.1-5000A)
25A(6.3-25A)
100A(25-100A)
250A(63-250A)
800A(250-800A)
Relay output contactor Rated negative capacity AC250V,10A
Switching input 10 channels passive dry contact(option DC110V,DC220V,AC220V)
Communication Standard 2 channels Modbus-RTU
Option(choose one)

1 or 2 channels Profibus DPV1

1 channel Profinet

Ethernet(Modbus TCP)

Environment Operation temperature -10℃~+55℃
Storage temperature -20℃~+65℃
Relative humidity ≤95%(No condensation)
Altitude ≤2000m
Class of pollution Level 3
Protection level Main module IP20
Installation category Class III