Multifunction Panel Energy Meter 0.5S APM800

● True RMS Measurements

● Unbalance & Phase Angles

● Demands and Multi-Tariff energy

● Max/Min Log with Timestamp

● Alarms and SOE Logs

● External Option module

description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
product detail

General

APM series power meters of ACREL are power meters that are designed according to IEC standards and synchronized with international advanced technology. APM series meters have full power measurement, energy statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of thequality of power supply network.

This series of meters use a modular design, with a rich function of the external DI / DO module, AI / AO module, event recording (SOE) module with T-Flash (TF) card, network communication module, can achieve full power measurement of electrical circuit and monitoring of switch status, Dual RS485 with Ethernet interface can realize data copying of RS485 master station, eliminating the need for data switching exchange. PROFIBUS-DP interface can realize high-speed data transmission and networking function.

Specification

Type Function
APM800

Measure all electric parameters (class 0.5s), Neutralcurrent, unbalance, mean, extremum

2DI+2DO, RS485 Communication (Modbus-RTU protocol)

APM801

Measure all electric parameters (class 0.2s), Neutralcurrent, unbalance, mean, extremum

2DI+2DO, RS485 Communication (Modbus-RTU protocol)

APM810
Measure all electric parameters (class 0.5s), Neutralcurrent, unbalance, mean, extremum

2DI+2DO, 2-63rd harmonic, RS485 Communication (Modbus-RTU protocol)

APM830
Measure all electric parameters (class 0.2s), Neutralcurrent, unbalance, mean, extremum

2DI+2DO, odd、even harmonic and total harmonic, RS485 Communication (Modbus-RTU protocol)

LCD Display

Dimension

Meter and panel opening size(unit: mm(in))

Multiple meter installation (unit: mm(in))

 


Wiring

Wiring sample of current and voltage


Typical Connection

 

Related Solution

Electric Energy Management System

parameter
Connection
3 phase 3 wire, 3 phase 4 wire
Frequency
50Hz
Input Voltage
Rated Voltage
AC 100V, 110V, 400V, 690V
Overload
1.2 times rated value(continuous); 2 times rated value(1 second)
Consumption
<0.5VA(per channel)
Input Current
Rated Voltage
AC 1A, 5A
Overload
1.2 times rated value(continuous); 2 times rated value(1 second)
Consumption
<0.5VA(per channel)
Accuracy
Voltage, current and power
Class 0.5S(APM800, APM810)

Class 0.2S(APM801, APM830)

Active power
Reactive power
Class 2
Harmonic
1%(2-42nd), 2%(43-63rd)
Switch inputs
Passive contact inputs, built-in power supply
Relay outputs
Contact type: open contact in main part, changeover contact in module
Pulse capacity: 3A/AC250V, 3A/DC30V
Pulse output of energy
Output mode: Optocoupler pulse with open collector
Pulse constant: 4000(5A), 8000(1A) imp/kWh
Analog output
DC0-20mA, 4-20mA, 0-5V, 1-5V output, accuracy class 0.5%,
Load resistance≤500Ω
Analog input
DC0-20mA, 4-20mA, 0-5V, 1-5V input, accuracy class 0.5%,
Storage card
Standard capacity: 4G, TF card up to 32G capacity
Communication
RS485(Modbus-RTU), Profibus(Profibus-DP),
Ethernet(Modbus-TCP, HTTP, DHCP)
Auxiliary power supply
AC/DC 85~265V or AC/DC 115~415V
Electromagnetic compatibility
IEC 61000 standard(Level 4)
Environment
Operating temperature
-20~65℃
Storing temperature
-20~70℃
Humidity
≤95%(No condensation)
Altitude
≤2500m

CONTACT US