Jiangsu Acrel Electrical Manufacturing Co., LTD.
tel:
+86 18761509710email:
besty.chen@email.acrel.cn● True RMS Measurements
● Unbalance & Phase Angles
● Demands and Multi-Tariff energy
● Max/Min Log with Timestamp
● Alarms and SOE Logs
● External Option module
General
APM series power meters of ACREL are power meters that are designed according to IEC standards and synchronized with international advanced technology. APM series meters have full power measurement, energy statistics, analysis of power quality and network communications and other functions, are mainly used for comprehensive monitoring of thequality of power supply network.
This series of meters use a modular design, with a rich function of the external DI / DO module, AI / AO module, event recording (SOE) module with T-Flash (TF) card, network communication module, can achieve full power measurement of electrical circuit and monitoring of switch status, Dual RS485 with Ethernet interface can realize data copying of RS485 master station, eliminating the need for data switching exchange. PROFIBUS-DP interface can realize high-speed data transmission and networking function.

Specification
| Type | Function |
| APM800 |
Measure all electric parameters (class 0.5s), Neutralcurrent, unbalance, mean, extremum 2DI+2DO, RS485 Communication (Modbus-RTU protocol) |
| APM801 |
Measure all electric parameters (class 0.2s), Neutralcurrent, unbalance, mean, extremum 2DI+2DO, RS485 Communication (Modbus-RTU protocol) |
| APM810 |
Measure all electric parameters (class 0.5s), Neutralcurrent, unbalance, mean, extremum
2DI+2DO, 2-63rd harmonic, RS485 Communication (Modbus-RTU protocol) |
| APM830 |
Measure all electric parameters (class 0.2s), Neutralcurrent, unbalance, mean, extremum
2DI+2DO, odd、even harmonic and total harmonic, RS485 Communication (Modbus-RTU protocol) |
LCD Display


Dimension

Meter and panel opening size(unit: mm(in))

Multiple meter installation (unit: mm(in))

Wiring
Wiring sample of current and voltage



Typical Connection

Related Solution
|
Connection
|
3 phase 3 wire, 3 phase 4 wire
|
|
|
Frequency
|
50Hz
|
|
|
Input Voltage
|
Rated Voltage
|
AC 100V, 110V, 400V, 690V
|
|
Overload
|
1.2 times rated value(continuous); 2 times rated value(1 second)
|
|
|
Consumption
|
<0.5VA(per channel)
|
|
|
Input Current
|
Rated Voltage
|
AC 1A, 5A
|
|
Overload
|
1.2 times rated value(continuous); 2 times rated value(1 second)
|
|
|
Consumption
|
<0.5VA(per channel)
|
|
|
Accuracy
|
Voltage, current and power
|
Class 0.5S(APM800, APM810)
Class 0.2S(APM801, APM830) |
|
Active power
|
||
|
Reactive power
|
Class 2
|
|
|
Harmonic
|
1%(2-42nd), 2%(43-63rd)
|
|
|
Switch inputs
|
Passive contact inputs, built-in power supply
|
|
|
Relay outputs
|
Contact type: open contact in main part, changeover contact in module
Pulse capacity: 3A/AC250V, 3A/DC30V
|
|
|
Pulse output of energy
|
Output mode: Optocoupler pulse with open collector
Pulse constant: 4000(5A), 8000(1A) imp/kWh |
|
|
Analog output
|
DC0-20mA, 4-20mA, 0-5V, 1-5V output, accuracy class 0.5%,
Load resistance≤500Ω
|
|
|
Analog input
|
DC0-20mA, 4-20mA, 0-5V, 1-5V input, accuracy class 0.5%,
|
|
|
Storage card
|
Standard capacity: 4G, TF card up to 32G capacity
|
|
|
Communication
|
RS485(Modbus-RTU), Profibus(Profibus-DP),
Ethernet(Modbus-TCP, HTTP, DHCP)
|
|
|
Auxiliary power supply
|
AC/DC 85~265V or AC/DC 115~415V
|
|
|
Electromagnetic compatibility
|
IEC 61000 standard(Level 4)
|
|
|
Environment
|
Operating temperature
|
-20~65℃
|
|
Storing temperature
|
-20~70℃
|
|
|
Humidity
|
≤95%(No condensation)
|
|
|
Altitude
|
≤2500m
|
|