Jiangsu Acrel Electrical Manufacturing Co., LTD.
tel:
+86 18761509710email:
besty.chen@email.acrel.cn
● Model: AKH-0.66/I 40I Low Voltage Solid Core CT
● Busbar Type/QTY: 40*10mm/1pcs
● Aperture: 30mm; Ratio: 10~1000/5(1)A
● Current transformer for AC measurement
● Suitable for cables or copper bus; Used with energy meters or relays
● 30I, 40I Optional Din Rail Mounted
General
They are patented and flip designed. The appearance is nice and the wiring is convenient. The transparent polycarbonate material is selected for the flip.We can clearly see the secondary lead wiring. It have square-round hole for both cable and bus passing through.
As alternating current signal acquisition element,it is generally matched with measuring instruments and widely used in electrical sets.
Specification
![]() |
|
|
![]() |
Dimension
Spec. and size (unit:mm)


| Type |
Outline size |
Through size |
Mounting size |
|||||
| Size |
W |
H |
D |
a |
e |
Φ |
M |
N |
|
30 I |
60 |
78 |
36 |
31 |
11 |
23 |
34 |
57.5 |
|
40 I |
75 |
95 |
45 |
42 |
11 |
31 |
40 |
57.5 |
|
60 I |
102 |
130 |
45 |
61.5 |
21 |
45 |
42 |
57.5 |
|
80 I |
118 |
140 |
45 |
82 |
11 |
52 |
60 |
57.5 |
Specification

Wiring

Installation

Fixed by Sheet Metal (Figure 1)

Fixed by Clutch Cover (with curved Support Plate) (Figure 2)

Fixed by Clutch Cover (with curved Support Plate) (Figure 3)

Fixed Installed on 35mm Standard DIN Rail (Figure 4)
Photo on Site

|
Specification
|
Rated Current Ratio(A)
|
Precision Degree and Corresponding Rated Load (VA)
|
Straight-Through Tums
|
Bus Spec(mm)/Number
|
Max. Cable Outer Diameter (mm) |
Installation
|
||
|
0.2
|
0.5
|
1
|
||||||
|
30I
|
15/5(1)
|
1.5
|
5
|
/
|
Ф22
|
A
|
||
|
20/5(1)
|
1.5
|
4
|
||||||
|
25-30/5(1)
|
1.5
|
3
|
||||||
|
40-60/5(1)
|
1.5
|
2
|
||||||
|
75-100/5(1)
|
1.5
|
1
|
30×10/1
|
A、B
|
||||
|
150-200/5(1)
|
2.5
|
1
|
||||||
|
250/5(1)
|
3.75
|
1
|
||||||
|
300-450/5(1)
|
5
|
1
|
||||||
|
500/5(1)
|
10
|
1
|
||||||
|
600/5
|
10
|
1
|
||||||
|
40I
|
10/5(1)
|
1.5
|
10
|
/
|
Ф30
|
A
|
||
|
15/5(1)
|
1.5
|
8
|
||||||
|
20/5(1)
|
|
1.5
|
5
|
|||||
|
25-30/5(1)
|
1.5
|
4
|
||||||
|
40/5(1)
|
1.5
|
3
|
||||||
|
50-75/5(1)
|
1.5
|
2
|
||||||
|
100/5(1)
|
1.5
|
1
|
40×10/1
|
A、C
|
||||
|
150/5(1)
|
2.5
|
1
|
||||||
|
200/5(1)
|
2.5
|
1
|
||||||
|
250/5(1)
|
3.75
|
1
|
||||||
|
300-450/5(1)
|
5
|
1
|
||||||
|
500-800/5(1)
|
10
|
1
|
||||||
|
1000/5(1)
|
10
|
1
|
||||||
|
60I
|
150/5(1)
|
2.5
|
1
|
60×10/1
60×6/1-2
|
Ф44
|
A、C
|
||
|
200-250/5(1)
|
2.5
|
1
|
||||||
|
300-450/5(1)
|
5
|
1
|
||||||
|
500-800/5(1)
|
10
|
1
|
||||||
|
1000-1250/5(1)
|
10
|
1
|
||||||
|
1500-2000/5(1)
|
20
|
1
|
||||||
|
2500/5(1)
|
30
|
1
|
||||||
|
80I
|
150/5(1)
|
2.5
|
1
|
80×10/1
|
Ф50
|
A、C
|
||
|
200-250/5(1)
|
2.5
|
1
|
||||||
|
300-400/5(1)
|
5
|
1
|
||||||
|
500-800/5(1)
|
10
|
1
|
||||||
|
1000-1250/5(1)
|
10
|
1
|
||||||
|
1500-2000/5(1)
|
20
|
1
|
||||||
|
2500-3000/5(1)
|
30
|
1
|
||||||