AITR Series Isolating Transformer

● Isolating transformers for medical IT systems
● Double insulation treatment, Electrostatic shielding layer
● PT100 temperature sensor
● Rated power: 3.15…10KVA
● CE
description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
product detail

General

AITR series isolation transformer is specially used in medical IT system, and the core superposition adopts the silicon steel sheet imported from Japan, which has very small losses. The windings are treated with double insulation and have electrostatic shielding layer, which reduces electromagnetic interference between windings. The PT100 temperature sensor is installed in the wire bag to monitor the temperature of transformer. The whole body is treated with vacuum invasion paint, which increases mechanical strength and corrosion resistance. The product has good temperature rise performance and very low noise.

Product Selection

Dimension

    Fig1 External dimensions of AITR series medical isolation transformer

     

    Type

    Capacity (VA)

    A(mm)

    B(mm)

    C(mm)

    D(mm)

    E(mm)

    F(mm)

    Totalweight (kg) (mm) (mm) (kg)

    AITR10000

    10000

    280

    275

    427

    240

    190

    φ11

    92

    AITR8000

    8000

    280

    265

    427

    240

    190

    φ11

    90

    AITR6300

    6300

    280

    255

    427

    240

    175

    φ11

    75

    AITR5000

    5000

    280

    255

    427

    240

    175

    φ11

    73

    AITR3150

    3150

    280

    225

    427

    240

    175

    φ11

    53

    Installation & Wiring

    Note:

    1) The S terminal wiring can select 2×4mm² yellow-green wire. The wiring of two ST terminals can select 2×1.5mm² shielded twisted pairs, and the wiring should not be too long.

    2) The connection line diameter of the input and output of the isolation transformer should match the rated current of the isolation transformer, or it can be selected according to the following table:

     

    Isolation transformer type

    Selected linediameter

    AITR3150

    3×4mm²

    AITR5000/AITR6300

    3×6mm²

    AITR8000/AITR10000

    3×10mm²

    Typical Connection

      PARAMETER

      Rated Capacity

      3.15kVA/5kVA/6.3kVA/8kVA/10kVA

      Frequency

      50/60Hz

      Rated input voltage

      230V

      The output voltage

      230V/115V

      Inrush current(IE)

      <12In

      Leakage Current

      <200uA

      No-load output voltage(UO)

      <235V

      No-load output current(IO)

      <3% In

      Short-circuit voltage

      <3% Un

      Efficiency

      >96%

      Maximum ambient temperature

      <40

      No-load temperature rise

      <33

      Full load temperature rise

      <76

      Withstand voltage

      4200V/Min

      Insulation Class

      H

      Noise Level

      <40dB (A)

      ISOLATION POWER CABINET

      CONTACT US