Ground Fault Detection And Location Relay

● Insulation fault location in AC IT systems
● AIL150-4: 4 measuring channels
● AIL150-8: 8 measuring channels
● LED indicators: On, Com
● CAN bus
● Auxiliary power supply: DC24V
description1
Zipper closure 1/5 zip athletic pullovers for men. Stretchy, lightweight, fast-drying fabric for superior performance. REGULAR FIT - US standard sizes. An athletic fit that sits close to the body for a wide range of motion, designed for optimal performance and all day comfort. FEATURES - Quarter zip closure;Thumbholes on long sleeves to keep them in place during workout
product detail

General

AIL150-4/AIL150-8 insulation fault locator uses high-precision signal detection circuit with high sensitivity transformer. It detects ASG150 test signal generator' s signal which is injected into the system. It can accurately locate the insulation fault circuit. Among them, AIL150-4 insulation fault locator can locate insulation faults of four loops, AIL150-8 insulation fault locator can locate insulation faults of eight loops.

Function

* Insulation fault location in medical IT systems.
* 4 or 8 channels with measuring current transformer per AIL150.
* Up to 16 measuring channels can be combined by can bus in one medical IT system.
* Aresponse time of up to 2 s in medical IT system acc. to IEC61557-9.

 

Product Selection

Dimension

fault locator_副本

 

Wiring

 

Typical Connection

Projects

1. Acrel Medical Isolated Power Supply System in Luanda General Hospital, Angola
2. ACREL Hospital Isolated Power Supply Application in Malaysia

IT PROJECTS

SELECTION

Acrel Medical IT System Insulation Monitoring and Fault Location Products Selection Table V1.0

Note“□”is optional“—”is not optional“■”is selection.

Medical Single Phase Isolation Transformer

AITR-3150

AITR-5000

AITR-6300

AITR-8000

AITR-10000

Capacity

3150VA

5000VA

6300VA

8000VA

10000VA

Insulation monitor

AIM-M10

AIM-M100

AIM-M200

Power supply

AC220±10%

AC85~265V

DC100-300V

DC24V

Communication

RS485

RS485+RS485

RS485+CAN

Output

DO1(over temperature)

DO1(over temperature)

DO2(alarm)

DO1(over temperature)

DO2(alarm) DO3(programmable)

1 channel DC24V

Support fault location

No

Yes

Power supply

ACLP10-24

HDR-60-24

Insulation monitor

AIM-M100

AIM-M200

Alarm indicator

AID10

AID120

AID150

AID200

Display

LED

LCD

Multi-machine display

No

Yes

Current transformer

AKH-0.66P26

Test signal generator

ASG150

Support fault location

No

Yes

Fault locator

AIL150-4

AIL150-8

Support fault location

No

Yes

Locate number of channels

<=4

>4; <8

>8 Note 1

Other

Note: 1. More than 8 channels can be freely combined, and the maximum support 24 locate channels.

 

Ordering example

Example 1: Isolation transformer 8kVA; AC220V; Insulation monitoring; Operating room LCD display; DO output programmable,According to the selection table, confirm the model is AITR-8000, AIM-M100, ACLP10-24, AKH-0.66P26, AID150.
Example 2: Isolation transformer 10kVA; Insulation monitoring; Fault location; ICU LCD display; DO output; Locate 12 loops;
According to the selection table, confirm the model is AITR-10000, AIM-M200, HDR-60-24, AKH-0.66P26, AID150, ASG150, AIL150-4, AIL150-8

parameter
Parameter
Value
AIL150-4
AIL150-8
Auxiliary power
Voltage
DC24V(±25%)
The maximum power consumption
≤2VA
Monitored system
Rated voltage
0-242VDC
Frequency
45-60HZ
Location signals
Location voltage
<25V
Location current
<1mA
Fault location
the maximum number of loops
4
8
Response time
<2S
Communication
Bus
CAN
Protocol
Custom protocol



 

 

 

 

 

 

 

 

 

 

 

 

ISOLATION POWER CABINET